SECTION 5 TECHNICAL DATA
Form 150.63-NM9
Issue date: 5/20/2021
5
Dimensions – YCUL0020 to 0072 (SI)
50 HZ MODEL 0020EE 0024EE 0031EE 0035EE 0045EE 0051EE 0055EE 0065EE 0072EE
Length L 2788.7 2788.7 3012.4 3012.4 3677.9 3677.9 3779.5 3779.5 3901.4
Width W 1135.4 1135.4 1135.4 1135.4 2301.2 2301.2 2301.2 2301.2 2301.2
Height H 1169.9 1169.9 1270.0 1270.0 1214.1 1214.1 1590.0 1590.0 1590.0
F
P 322.6 322.6 424.2 424.2 345.4 345.4 723.9 723.9 723.9
Connection
Sizes
Suction In 1 40.6 40.6 53.3 53.3 53.3 53.3 53.3 53.3 58.4
Suction In 2 53.3
Liquid Out 1 / 2 22.9 22.9 27.9 27.9 27.9 27.9 27.9 27.9 27.9
System 1
Dimensions
Suction In 957.6 957.6 157.5 99.1 1237.0 1237.0 1338.6 1127.8 1364.0
Liquid Out 805.2 805.2 586.7 878.8 1851.7 1851.7 2161.5 2161.5 1971.0
System 2
Dimensions
Suction In 1056.6 1056.6 891.5 891.5 845.8
Liquid Out 439.4 439.4 358.1 358.1 381.0
D1 772.2 772.2 734.1 503 497.8 500.4 609..6 246.4 172.7
D2 152.4 152.4 165.1 147.3 162.6 162.6 231.1 231.1 134.6
D3 350.5 350.5 233.7
D4
Isolator
Location
Dimensions
I1 431.8 431.8 431.8 431.8 248.9 248.9 248.9 248.9 248.9
I2 2646.7 2646.7 2877.8 2877.8 3429.0 3429.0 3429.0 3429.0 3652.5
I3
I4
I5
I6
I7
I8
A 27.9 27.9 27.9 27.9 27.9 27.9 27.9 27.9 27.9
B 1099.8 1099.8 1099.8 1099.8 2273.2 2273.2 2273.2 2273.2 2273.2
Rigging
Hole
Locations
R1 396.2 396.2 396.2 396.2 383.5 383.5 383.5 383.5 383.5
R2 2466.6 2466.6 2669.5 2669.5 3324.9 3324.9 3324.9 3322.3 3495.0
R3
R4
Unit COG
X 1488.4 1485.9 1602.7 1704.3 1513.8 1503.7 1572.3 1562.1 1516.4
Y 581.7 581.7 581.7 586.7 1107.4 1104.9 1071.9 1071.9 1140.5