Electrical Data
Table 5: Electrical Data - Outdoor Unit
Model
Compressors Outdoor Fan Motor
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
YD360
208/230-3-60 4 25.0 39 164 208/230-3-60 1 1/2 4 5.8 129.5 150
460-3-60 4 12.2 19 100 460-3-60 1 1/2 4 2.9 63.5 70
575-3-60 4 9.0 14 78 575-3-60 1 1/2 4 2.2 47.1 50
YD480
208/230-3-60 4 30.1 47 225 208/230-3-60 1 1/2 4 5.8 151.1 175
460-3-60 4 16.7 26 114 460-3-60 1 1/2 4 2.9 82.6 90
575-3-60 4 12.2 19 80 575-3-60 1 1/2 4 2.2 60.7 70
YD600
208/230-3-60 4 48.1 75 245 208/230-3-60 1 1/2 4 5.8 227.6 250
460-3-60 4 18.6 29 125 460-3-60 1 1/2 4 2.9 90.7 100
575-3-60 4 14.7 23 100 575-3-60 1 1/2 4 2.2 71.3 80
1. Maximum fuse or maximum circuit breaker (HACR type per NEC).
2. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.