Johnson Controls Unitary Products 27
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD42S41S4
INDOOR COIL MODEL NO. AHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 42.5 44.2 45.0 49.4 52.7 44.4 45.8 46.4 50.5 53.5 46.4 47.4 47.7 51.5 54.4
S.C. 42.5 38.4 32.9 32.8 26.7 44.4 42.2 35.3 34.7 27.6 46.4 46.0 37.6 36.7 28.6
KW 2.7 2.8 2.8 2.8 2.9 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.9 3.0 3.0
75
T.C. 39.9 40.7 41.7 46.3 49.8 41.8 42.3 42.9 47.2 50.6 43.7 43.9 44.1 48.1 51.3
S.C. 39.9 36.8 31.4 31.4 25.4 41.8 40.0 33.7 33.3 26.4 43.7 43.2 36.0 35.3 27.4
KW 2.9 2.9 2.9 3.0 3.1 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2 3.2
85
T.C. 37.4 37.3 38.4 43.2 47.0 39.2 38.8 39.5 44.0 47.6 41.0 40.4 40.6 44.8 48.3
S.C. 37.4 35.1 29.8 29.9 24.1 39.2 37.8 32.1 32.0 25.1 41.0 40.4 34.4 34.0 26.1
KW 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.4 3.4
95
T.C. 34.8 33.9 35.0 40.1 44.1 36.6 35.4 36.0 40.7 44.7 38.3 36.8 37.0 41.4 45.3
S.C. 34.8 33.4 28.3 28.5 22.8 36.6 35.4 30.6 30.6 23.8 38.3 36.8 32.8 32.6 24.8
KW 3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.6 3.6
105
T.C. 31.6 31.2 30.9 36.1 40.5 33.4 32.8 31.7 37.1 41.2 35.3 34.5 32.6 38.0 42.0
S.C. 31.6 31.2 26.5 26.9 21.3 33.4 32.8 28.6 29.1 22.4 35.3 34.5 30.8 31.3 23.6
KW 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.6 3.7 3.8 3.8 3.7 3.7 3.8 3.9
115
T.C. 28.3 28.5 26.7 32.1 36.9 30.3 30.3 27.4 33.4 37.8 32.2 32.1 28.1 34.7 38.6
S.C. 28.3 28.5 24.6 25.3 19.7 30.3 30.3 26.7 27.6 21.0 32.2 32.1 28.1 29.9 22.4
KW 3.7 3.7 3.6 3.8 3.9 3.8 3.8 3.7 3.9 4.0 4.0 4.0 3.8 4.0 4.1
125
T.C. 25.1 25.8 22.6 28.1 33.3 27.1 27.8 23.1 29.7 34.3 29.1 29.7 23.7 31.3 35.3
S.C. 25.1 25.8 22.6 23.6 18.1 27.1 27.8 23.1 26.1 19.6 29.1 29.7 23.7 28.6 21.2
KW 3.9 3.9 3.8 4.0 4.2 4.0 4.0 3.9 4.1 4.3 4.2 4.2 4.0 4.2 4.4
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC60 1.00 1.03 1.05
– HD60 1.00 1.01 1.05
– UC60 0.99 1.00 1.04
AHE48D – 1.01 1.03 1.02
AHP60 – 1.02 1.05 0.95
AHR48D – 0.98 0.96 1.02
AHX42 – 0.99 1.05 0.95
AHX48 – 1.02 1.06 0.99
AV*48 – 1.02 1.05 0.99
AV*60 – 1.02 1.05 0.99
F4FP045 – 1.00 1.03 1.05
F4FV060 – 0.99 0.99 0.98
F5FP060 – 1.02 1.07 0.99
F6FP048 – 1.02 1.05 0.99
MX16C FC/MC48C 1.01 1.02 0.97
MX20D FC/MC48D 1.01 1.02 0.97
MX16C FC60C 1.02 1.05 0.99
MX20D FC/MC60D 1.02 1.05 0.99
MV16C FC/MC48C 1.02 1.02 0.95
MV16C FC60C 1.01 1.05 0.97
MV20D FC/MC48D 1.03 1.04 0.93
MV20D FC/MC60D 1.02 1.05 0.99
Air Handlers Coils T.C. S.C. KW