571209-YTG-B-1211
Johnson Controls Unitary Products 29
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD48S41S4
INDOOR COIL MODEL NO. AHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1510 1710 1910
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 47.6 50.1 49.8 54.1 60.7 49.4 50.8 51.0 55.8 61.9 51.2 51.5 52.2 57.5 63.1
S.C. 47.6 44.7 37.8 37.0 30.4 49.4 48.3 39.9 39.3 31.5 51.2 51.5 42.0 41.6 32.6
KW 2.9 2.9 2.9 3.0 3.0 3.0 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2
75
T.C. 45.1 46.6 46.5 50.8 56.9 46.7 47.2 47.5 52.2 58.0 48.4 47.9 48.5 53.6 59.0
S.C. 45.1 43.1 36.2 35.6 28.9 46.7 45.8 38.3 37.8 30.0 48.4 47.9 40.3 40.0 31.1
KW 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.4 3.4
85
T.C. 42.5 43.1 43.2 47.5 53.2 44.1 43.7 44.0 48.6 54.1 45.6 44.3 44.7 49.7 55.0
S.C. 42.5 41.5 34.7 34.2 27.3 44.1 43.3 36.7 36.2 28.4 45.6 44.3 38.7 38.3 29.6
KW 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6 3.7
95
T.C. 40.0 39.6 39.9 44.2 49.4 41.4 40.2 40.4 45.0 50.2 42.8 40.7 41.0 45.8 51.0
S.C. 40.0 39.6 33.1 32.7 25.8 41.4 40.2 35.0 34.7 26.9 42.8 40.7 37.0 36.6 28.0
KW 3.6 3.6 3.6 3.7 3.8 3.7 3.7 3.7 3.8 3.9 3.8 3.8 3.8 3.9 4.0
105
T.C. 37.2 37.1 36.3 40.6 45.3 38.5 37.8 36.8 41.1 45.9 39.7 38.6 37.2 41.7 46.6
S.C. 37.2 37.1 31.6 31.3 24.2 38.5 37.8 33.5 33.2 25.2 39.7 38.6 35.4 35.1 26.3
KW 3.9 3.9 3.9 4.0 4.1 4.0 4.0 3.9 4.0 4.2 4.1 4.1 4.0 4.1 4.2
115
T.C. 34.5 34.5 32.8 36.9 41.1 35.5 35.5 33.1 37.2 41.6 36.6 36.4 33.5 37.6 42.1
S.C. 34.5 34.5 30.0 29.8 22.5 35.5 35.5 31.9 31.7 23.6 36.6 36.4 33.5 33.5 24.6
KW 4.1 4.1 4.1 4.2 4.3 4.2 4.2 4.2 4.3 4.4 4.4 4.4 4.3 4.4 4.5
125
T.C. 31.7 31.9 29.3 33.2 37.0 32.6 33.1 29.5 33.3 37.3 33.5 34.2 29.7 33.4 37.7
S.C. 31.7 31.9 28.5 28.3 20.9 32.6 33.1 29.5 30.1 21.9 33.5 34.2 29.7 31.9 22.9
KW 4.4 4.4 4.3 4.5 4.6 4.5 4.5 4.4 4.5 4.7 4.6 4.6 4.5 4.6 4.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC60 0.98 0.97 1.05
– FC/MC62 0.99 0.98 1.07
– UC60 0.98 0.95 1.05
AHE48D – 0.99 0.97 0.97
AHE60D – 1.00 1.02 0.93
AHP60 – 0.99 0.98 0.98
AHR48D – 0.98 0.95 1.04
AHR60D – 0.99 0.98 1.07
AHX48 – 1.01 1.01 1.00
AHX60 – 1.01 0.99 1.00
AV*48 – 1.00 0.99 0.99
AV*60 – 1.00 1.00 0.99
F4FV060 – 1.00 0.99 0.94
F5FP060 – 0.99 0.99 0.98
F6FP048 – 1.00 0.99 0.99
F6FP060 – 1.01 0.99 1.00
MX16C FC60C 1.02 1.01 1.00
MX20D FC/MC60D 1.02 1.01 1.00
MX20D FC/MC62D 1.01 1.00 0.99
MV16C FC60C 0.98 0.97 1.01
MV20D FC/MC60D 0.99 0.98 0.98
MV20D FC/MC62D 1.01 0.99 1.00
Furnaces Coils T.C. S.C. KW
T*(8,L)X*C16 FC/PC60C 0.99 0.98 0.98
T*(8,L)X*C20 FC/PC60C 0.99 0.98 0.98
T*9X*C16 FC/PC60C 0.99 0.98 0.98
T*9X*C20 FC/PC60C 0.99 0.98 0.98
T*9X*D20 FC/MC/PC60D 1.01 0.97 1.00
T*(8,L)X*C16 FC/MC62D 1.00 0.99 0.99
T*(8,L)X*C20 FC/MC62D 1.01 0.99 1.00
T*9X*C16 FC/MC62D 1.00 0.99 0.99
T*9X*C20 FC/MC62D 1.00 0.99 0.99
T*9X*D20 FC/MC62D 1.00 0.99 0.99
T*(8,L)X*C16 UC60C 0.99 0.96 0.98
T*(8,L)X*C20 UC60C 1.00 0.97 0.99
T*9X*C16 UC60C 0.99 0.96 0.98
T*9X*C20 UC60C 0.99 0.96 0.98
T*9X*D20 UC60D 0.99 0.95 0.98
(Y*LC/T*8V/T*LV)*C16 FC/PC60C 0.98 0.97 0.97
(Y*LC/T*8V/T*LV)*C20 FC/PC60C 0.98 0.97 0.96
(Y*9C/T*9V)*C16 FC/PC60C 0.98 0.97 0.97
(Y*9C/T*9V)*C20 FC/PC60C 0.98 0.97 0.97
(Y*9C/T*9V)*D20 FC/MC/PC60D 0.99 0.97 0.98
(Y*LC/T*8V/T*LV)*C16 FC/MC62D 1.00 0.99 0.99
(Y*LC/T*8V/T*LV)*C20 FC/MC62D 1.00 0.99 0.99
(Y*9C/T*9V)*C16 FC/MC62D 1.00 0.98 0.99
(Y*9C/T*9V)*C20 FC/MC62D 0.99 0.98 0.98
(Y*9C/T*9V)*D20 FC/MC62D 1.00 0.98 0.99
(Y*LC/T*8V/T*LV)*C16 UC60C 0.98 0.95 0.97
(Y*LC/T*8V/T*LV)*C20 UC60C 0.99 0.96 0.98
(Y*9C/T*9V)*C16 UC60C 0.98 0.95 0.97
(Y*9C/T*9V)*C20 UC60C 0.98 0.95 1.01
(Y*9C/T*9V)*D20 UC60D 0.98 0.95 0.97
Furnaces Coils T.C. S.C. KW