571209-YTG-B-1211
Johnson Controls Unitary Products 31
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJD18S41S2
EVAPORATOR COIL MODEL NO FC35
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
450 600 750
MBH COP KW MBH COP KW MBH COP KW
60
60 21.1 4.1 1.50 22.2 4.5 1.44 23.3 4.9 1.39
70 20.5 3.6 1.65 21.6 4.0 1.59 22.6 4.3 1.53
80 19.9 3.2 1.81 20.9 3.5 1.74 21.9 3.9 1.66
47
60 18.6 3.8 1.45 19.2 4.0 1.41 19.8 4.2 1.38
70 17.7 3.3 1.60 18.4 3.5 1.55 19.1 3.7 1.51
80 16.8 2.8 1.74 17.6 3.1 1.69 18.4 3.3 1.64
40
60 16.7 3.4 1.43 17.3 3.6 1.40 17.9 3.8 1.37
70 16.1 3.0 1.57 16.8 3.2 1.53 17.4 3.4 1.50
80 15.6 2.7 1.70 16.3 2.9 1.66 17.0 3.1 1.62
30
60 14.6 3.1 1.39 15.1 3.2 1.37 15.5 3.4 1.36
70 14.2 2.7 1.52 14.6 2.9 1.50 15.0 3.0 1.48
80 13.7 2.4 1.66 14.1 2.5 1.63 14.4 2.6 1.61
17
60 11.7 2.6 1.34 12.0 2.6 1.34 12.3 2.7 1.34
70 11.2 2.2 1.48 11.6 2.3 1.47 11.9 2.4 1.46
80 10.8 2.0 1.62 11.1 2.0 1.60 11.5 2.1 1.58
10
60 10.1 2.3 1.31 10.3 2.3 1.31 10.4 2.3 1.32
70 9.6 1.9 1.45 9.9 2.0 1.44 10.2 2.1 1.44
80 9.1 1.7 1.59 9.5 1.8 1.58 9.9 1.9 1.57
NOTE: ALL CAPACITIES ARE NET, WITH INDOOR FAN HEAT ALREADY DEDUCTED. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils MBH COP KW
FC/MC/PC18 1.00 1.00 1.00
FC/MC/PC24 1.03 1.04 0.99
HD24 0.97 0.96 1.02
AHE18B 0.93 1.08 0.86
AHP18 1.00 1.00 1.00
AHP24 1.00 1.00 1.00
AHR18B 0.93 1.03 0.90
AHX18 0.98 0.99 1.00
AV*24 – 0.98 0.99 1.00
F4FP024 – 1.01 1.01 1.00
F6FP018 0.98 0.99 1.00
F6FP024 0.98 0.99 1.00
MX12B FC/MC18B 0.93 1.08 0.86
MX12B FC/MC24B 0.93 1.16 0.80
MX12B FC/MC30B 0.93 1.16 0.80
MV12B FC/MC18B 0.98 0.98 1.00
MV12B FC/MC24B 1.00 1.02 0.99
Furnaces Coils MBH COP KW
T*(8,L)X*A12 FC/MC/PC18A 0.97 1.06 0.92
T*(8,L)X*B12 FC/MC/PC18B 0.97 1.06 0.92
T*9X*B12 FC/MC/PC18B 0.97 1.06 0.92
T*(8,L)X*A12 FC/MC/PC24A 0.99 1.10 0.90
T*(8,L)X*B12 FC/MC/PC24B 0.99 1.10 0.90
T*9X*B12 FC/MC/PC24B 0.99 1.10 0.90
T*(8,L)X*A12 FC/MC/PC30A 0.99 1.10 0.90
T*(8,L)X*B12 FC/MC/PC30B 0.99 1.10 0.90
T*9X*B12 FC/MC/PC30B 0.99 1.10 0.90
(Y*LC/T*8V/T*LV)*A12 FC/MC/PC18A 0.98 1.07 0.92
(Y*LC/T*8V/T*LV)*B12 FC/MC/PC18B 0.97 1.06 0.92
(Y*9C/T*9V)*B12 FC/MC/PC18B 0.98 1.07 0.92
(Y*LC/T*8V/T*LV)*A12 FC/MC/PC24A 1.01 1.10 0.92
(Y*LC/T*8V/T*LV)*B12 FC/MC/PC24B 0.99 1.10 0.90
(Y*9C/T*9V)*B12 FC/MC/PC24B 1.01 1.11 0.91
(Y*LC/T*8V/T*LV)*A12 FC/MC/PC30A 1.01 1.10 0.92
(Y*LC/T*8V/T*LV)*B12 FC/MC/PC30B 0.99 1.10 0.90
(Y*9C/T*9V)*B12 FC/MC/PC30B 1.01 1.11 0.91
(Y*LC/T*8V/T*LV)*A12 HD24 0.98 1.06 0.93
(Y*LC/T*8V/T*LV)*B12 HD24 0.96 1.04 0.92
(Y*9C/T*9V)*B12 HD24 0.98 1.07 0.92
(Y*LC/T*8V/T*LV)*A12 UC18A 0.99 1.08 0.92
(Y*LC/T*8V/T*LV)*B12 UC18B 0.98 1.07 0.92
(Y*9C/T*9V)*B12 UC18B 0.99 1.08 0.91
(Y*LC/T*8V/T*LV)*A12 UC24A 1.02 1.11 0.91
(Y*LC/T*8V/T*LV)*B12 UC24B 0.99 1.10 0.90
(Y*9C/T*9V)*B12 UC24B 1.01 1.12 0.91
(Y*LC/T*8V/T*LV)*A12 UC30A 1.01 1.11 0.91
(Y*LC/T*8V/T*LV)*B12 UC30B 0.99 1.10 0.90
(Y*9C/T*9V)*B12 UC30B 1.01 1.12 0.91
Furnaces Coils MBH COP KW