571209-YTG-B-1211
Johnson Controls Unitary Products 37
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJD48S41S4
EVAPORATOR COIL MODEL NO AHP48
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1400 1600 1800
MBH COP KW MBH COP KW MBH COP KW
60
60 53.4 3.7 4.17 53.2 3.7 4.17 53.1 3.7 4.16
70 51.9 3.5 4.32 52.0 3.5 4.31 52.2 3.6 4.30
80 50.4 3.3 4.45 50.8 3.3 4.46 51.3 3.4 4.46
47
60 46.3 3.6 3.75 46.6 3.6 3.77 46.9 3.6 3.78
70 46.5 3.7 3.71 46.0 3.5 3.84 45.5 3.4 3.97
80 46.7 3.7 3.68 45.4 3.5 3.84 44.2 3.2 4.01
40
60 42.6 3.5 3.52 42.8 3.5 3.55 43.0 3.5 3.58
70 39.8 3.3 3.57 40.3 3.3 3.61 40.8 3.3 3.65
80 37.0 3.0 3.63 37.8 3.0 3.68 38.7 3.0 3.72
30
60 32.1 3.1 3.04 33.2 3.1 3.12 34.4 3.1 3.21
70 31.7 2.9 3.16 32.7 3.0 3.24 33.7 3.0 3.31
80 31.4 2.8 3.29 32.2 2.8 3.36 32.9 2.8 3.42
17
60 27.2 2.8 2.82 28.1 2.9 2.88 29.0 2.9 2.95
70 26.6 2.7 2.89 27.6 2.7 2.98 28.5 2.7 3.07
80 24.2 2.4 2.96 25.1 2.4 3.05 26.1 2.4 3.14
10
60 23.1 2.6 2.62 24.4 2.6 2.72 25.7 2.7 2.83
70 21.7 2.3 2.71 22.7 2.4 2.81 23.7 2.4 2.91
80 20.3 2.1 2.80 21.1 2.1 2.90 21.8 2.1 2.99
NOTE: ALL CAPACITIES ARE NET, WITH INDOOR FAN HEAT ALREADY DEDUCTED. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils MBH COP KW
FC/MC/PC60 0.99 1.02 0.97
FC/MC62 0.99 1.01 0.98
UC60 0.99 1.02 0.97
AHE48D 0.98 1.05 0.93
AHE60D 0.98 1.06 0.93
AHP60 0.98 1.06 0.93
AHR48D 0.99 1.02 0.97
AHR60D 0.99 1.02 0.97
AHX48 0.97 1.05 0.92
AHX60 0.97 1.07 0.91
AV*48 0.99 1.08 0.92
AV*60 0.98 1.09 0.90
F4FV060 0.99 1.07 0.93
F5FP060 0.99 1.06 0.94
F6FP048 0.99 1.07 0.92
F6FP060 0.97 1.07 0.91
MX16C FC60C 0.98 1.09 0.90
MX20D FC/MC60D 0.98 1.10 0.89
MX20D FC/MC62D 0.98 1.09 0.90
MV16C FC60C 0.99 1.02 0.97
MV20D FC/MC60D 0.98 1.06 0.92
MV20D FC/MC62D 0.97 1.06 0.91
Furnaces Coils MBH COP KW
T*(8,L)X*C16 FC/PC60C 0.98 1.06 0.93
T*(8,L)X*C20 FC/PC60C 0.98 1.06 0.92
T*9X*C16 FC/PC60C 0.98 1.06 0.93
T*9X*C20 FC/PC60C 0.98 1.07 0.92
T*9X*D20 FC/MC/PC60D 0.96 1.09 0.88
T*(8,L)X*C16 FC/MC62D 0.98 1.05 0.94
T*(8,L)X*C20 FC/MC62D 0.97 1.06 0.92
T*9X*C16 FC/MC62D 0.98 1.05 0.94
T*9X*C20 FC/MC62D 0.97 1.05 0.92
T*9X*D20 FC/MC62D 0.98 1.04 0.94
T*(8,L)X*C16 UC60C 0.98 1.05 0.93
T*(8,L)X*C20 UC60C 0.96 1.09 0.88
T*9X*C16 UC60C 0.98 1.05 0.94
T*9X*C20 UC60C 0.97 1.06 0.92
T*9X*D20 UC60D 0.96 1.07 0.89
(Y*LC/T*8V/T*LV)*C16 FC/PC60C 0.99 1.04 0.95
(Y*LC/T*8V/T*LV)*C20 FC/PC60C 0.99 1.04 0.95
(Y*9C/T*9V)*C16 FC/PC60C 0.99 1.03 0.96
(Y*9C/T*9V)*C20 FC/PC60C 0.99 1.03 0.96
(Y*9C/T*9V)*D20 FC/MC/PC60D 0.99 1.04 0.95
(Y*LC/T*8V/T*LV)*C16 FC/MC62D 0.98 1.04 0.94
(Y*LC/T*8V/T*LV)*C20 FC/MC62D 0.98 1.05 0.94
(Y*9C/T*9V)*C16 FC/MC62D 0.98 1.03 0.95
(Y*9C/T*9V)*C20 FC/MC62D 0.98 1.02 0.96
(Y*9C/T*9V)*D20 FC/MC62D 0.98 1.03 0.95
(Y*LC/T*8V/T*LV)*C16 UC60C 0.98 1.03 0.95
(Y*LC/T*8V/T*LV)*C20 UC60C 0.98 1.05 0.93
(Y*9C/T*9V)*C16 UC60C 0.98 1.02 0.96
(Y*9C/T*9V)*C20 UC60C 0.98 1.02 0.96
(Y*9C/T*9V)*D20 UC60D 0.98 1.03 0.95
Furnaces Coils MBH COP KW