571209-YTG-B-1211
4 Johnson Controls Unitary Products
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator, and 15 feet of interconnecting
line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for evap-
orator + charge adder for line set.
F6FP024 .051/ TXV + 5 ––––––
F6FP030 – .059 / TXV + 0 .063 / TXV + 0 ––––
F6FP036 – .059 / TXV + 0 .063 / TXV + 0 ––––
F6FP042 – – – .071 / TXV + 16 – – –
F6FP048 – – – – .075 / TXV + 0 TXV + 0 –
F6FP060 –––––TXV + 25TXV + 0
HD24 .051/ TXV + 0 ––––––
HD48 – – – .071 / TXV + 16 – – –
HD60 – – – – .075 / TXV + 0 – –
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil only
matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
4. Refer to Cooling and Heating Performance Data tables for actual performance for specified system matches.
System Charge for Various Matched Systems (Continued)
Outdoor Unit YHJD18S41S2 YHJD24S41S4 YHJD30S41S4 YHJD36S41S4 YHJD42S41S4 YHJD48S41S4 YHJD60S41S4
Required Orifice or TXV
1
.051/4F1 .054/4G1 .063/4G1 .071/4H1 .075/4H1 4J1 4K1
Factory Charge, lbs-oz 6 - 6 9 - 6 9 - 0 10 - 0 9 - 10 14 - 2 13 - 13
Indoor Coil
2,3,4
Additional Charge, Oz
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL WIDTH
RATED
CFM
NET MBH
SEER EER
TOTAL SENS.
13 SEER AC WITH AIR HANDLERS
YHJD18S41S2
AHE18B 17 – 610 18.0 14.6 14.00 12.00
AHP18 17 – 600 18.0 14.0 13.00 11.00
AHP24 17 – 600 18.0 14.0 13.00 11.00
AHR18B 17 – 665 18.0 14.9 13.00 11.00
AHX18 17 – 600 18.0 14.0 14.50 12.00
AV*24 17 – 550 18.0 13.7 14.00 12.00
F4FP024 17 – 600 18.0 14.0 13.00 11.00
F6FP018 17 – 600 18.0 14.0 14.50 12.00
F6FP024 17 – 610 18.0 14.0 14.50 12.00
MV12B 17 FC/MC18B 600 18.0 13.7 14.00 12.00
MV12B 17 FC/MC24B 600 18.0 13.7 14.00 12.00
MX12B 17 FC/MC18B 585 18.0 14.5 14.50 12.00
MX12B 17 FC/MC24B 645 18.0 15.0 14.50 12.00
MX12B 17 FC/MC30B 645 18.0 15.0 14.50 12.00
YHJD24S41S4
AHE24B 17 – 795 24.0 17.4 14.50 12.00
AHE30B 17 – 795 24.0 17.4 14.50 12.00
AHP30 17 – 800 23.8 17.1 13.00 11.00
AHR24B 17 – 740 24.0 16.9 13.00 11.00
AHR30B 17 – 740 24.0 16.9 13.00 11.00
AHX30 17 – 820 24.0 17.5 14.00 12.00
AHX36 21 – 820 24.0 17.5 14.00 12.00
AV*36 21 – 725 24.0 17.0 14.50 12.00
For Notes See Page 6.