SECTION 4 - PRINTING
YORK TREND
CHILLER ID 163
© 1997 – 2000 YORK INTERNATIONAL CORPORATION
MON 09 OCT 2000 3:33:47 PM
DATA 1: LEAVING CHILLED LIQUID TEMPERATURE
DATA 2: RETURN CHILLED LIQUID TEMPERATURE
DATA 3: EVAPORATOR PRESSURE
DATA 4: LEAVING CONDENSER LIQUID TEMPERATURE
DATA 5: RETURN CONDENSER LIQUID TEMPERATURE
DATA 6: CONDENSER PRESSURE
TIME DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6
3:33:47 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:48 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:49 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:50 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.3 °F 120.1 PSIG
3:33:51 PM 45.5 °F 55.2 °F 39.1 PSIG 95.1 °F 85.4 °F 120.2 PSIG
FIGURE 71 - SAMPLE PRINTOUT (TREND DATA
NEW OR EXISTING POINTS)
FIGURE 70 - SAMPLE PRINTOUT (SECURITY LOG
REPORT)
YORK SETPOINT CHANGE LOG
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Fri 05 Oct 2001 4:48:04 PM
Log Entry 1 Evaporator - Leaving Chilled Local Setpoint
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 4:23:49 PM
Access Level = Service
User Id = 4268
Old Value = 46.5 ~F
New Value = 48.0 ~F
Log Entry 2 Condenser - High Pressure Warning Threshold
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:36:12 PM
Access Level = Service
User Id = 4268
Old Value = 162.5 Psig
New Value = 225.0 Psig
Log Entry 3 Condenser - Drop Leg
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:36:02 PM
Access Level = Service
User Id = 4268
Old Value = Disabled
New Value = Enabled
Log Entry 4 Evaporator - Refrigerant
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:35:48 PM
Access Level = Service
User Id = 4268
Old Value = Disabled
New Value = Enabled
FIGURE 72 - SAMPLE PRINTOUT (CUSTOM
SCREEN REPORT)
YORK CUSTOM VIEW
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 21 Jun 1999 1:28:25 PM
Leaving Chilled Liquid Temperature = 45.0 ~F
Return Chilled Liquid Temperature = 55.0 ~F
Leaving Condenser Liquid Temperature = 95.0 ~F
Return Condenser Liquid Temperature = 85.0 ~F
Evaporator Saturation Temperature = 41.0 ~F
Condenser Saturation Temperature = 78.5 ~F
Evaporator Pressure = 70.0 Psig
Condenser Pressure = 140.0 Psig
Oil Pressure = 45.0 Psid
% Full Load Amps = 50 %