EasyManua.ls Logo

York YK Series - Page 48

York YK Series
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM 160.54-O1
ISSUE DATE: 9/10/2014
JOHNSON CONTROLS
48
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
PROGRAMMABLE
Valve Preset Time
Upon entering chiller prelube, the Refrigerant Level
close output is energized for the length of the program-
mable Valve Preset Time Setpoint (0 to 100 seconds;
default 50).
Ramp-up Time
This ramp limit allows the level to go from the present
level to the Refrigerant Level Setpoint over a period of
time programmed as the Ramp-Up Time Setpoint (3 to
15 minutes; default 8).
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Condenser
Access Level Required: VIEW
Returns user to CONDENSER Screen.
Setpoints
Access Level Required: SERVICE
Moves to a subscreen allowing programming of the
Refrigerant Level Control Setpoints.

Table of Contents

Other manuals for York YK Series

Related product manuals