JOHNSON CONTROLS
48
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
SECTION 5 – TECHNICAL DATA
ELECTRICAL DATA
TABLE 6 - MICROPANEL POWER SUPPLY
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC SW
MIN MAX
MODELS W/O
CONTROL
TRANS
115-1-60/50
15A 10A 15A 30 A / 240V
MODELS W/
CONTROL
TRANS
-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V
-40 380-1-60 15A 10A 15A 30 A / 480V
-46 460-1-60 15A 10A 15A 30 A / 480V
-50 380/415-1-60 15A 10A 15A 30A / 415V
-58 575-1-60 15A 10A 15A 30 A / 600V
A. Minimum #14 AWG, 75 °C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
TABLE 7 - VOLTAGE RANGE
VOLTAGE RANGE
VOLTAGE CODE UNIT POWER MIN. MAX.
-17
200/3/60 180 220
208/3/60 187 228
-28 230-3-60 207 253
-40 380-3-60 355 415
-46 460-3-60 414 506
-50 380/415-3-50 360 440
-58 575-3-60 517 633
COMPRESSOR HEATERS
Compressor heaters are standard. ZP180 compressors
utilize 70W heaters; ZP235, compressor use 120W
heaters and ZP285, ZP385, and ZP485 utilize 150W
heaters. If power is OFF more than two hours, the
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
PRIOR to working on equipment.
The unit evaporator heater uses 120VAC.
Disconnecting 120VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
crankcase heaters must be energized for 18 – 24 hours
prior to restarting a compressor. This will assure that
liquid slugging and oil dilution does not damage the
compressors on start.