SECTION 5 – TECHNICAL DATA
TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS
CHILLER
MODEL
VOLTAGE
CODE
MIN CKT.
AMPS
MIN N/F
DISC SW
MIN DUAL
ELEM
FUSE &
MIN CB
MAX DUAL
ELEM
FUSE
MAX CB
58
208 276 400 300 300
230 275 400 300 300
380 149 200 175 175
460 130 200 150 150
575 103 150 110 110
65
208 306 400 350 350
230 305 400 350 350
380 170 250 200 200
460 150 200 175 175
575 112 150 125 125
70
208 334 400 350 350
230 333 400 350 350
380 191 250 225 225
460 169 200 175 175
575 120 150 125 125
80
208 363 600 400 400
230 363 600 400 400
380 201 250 225 225
460 177 250 200 200
575 134 200 150 150
81
208 363 400 400 400
230 363 400 400 400
380 201 250 225 225
460 177 250 200 200
575 134 200 150 150
89
208 391 600 450 450
230 390 600 450 450
380 211 250 250 250
460 184 250 200 200
575 146 200 150 150
92
208 406 600 450 450
230 405 600 450 450
380 220 400 250 250
460 192 250 225 225
575 152 200 150 150
100
208 450 600 500 500
230 449 600 500 500
380 260 400 300 300
460 220 400 250 250
575 175 250 200 200
101
208 458 600 500 500
230 456 600 500 500
380 264 400 300 300
460 224 400 250 250
575 178 250 200 200
120
208 497 800 600 600
230 496 800 600 600
380 300 400 350 350
460 250 400 300 300
575 198 250 225 225