55
CHILLER
MODEL
VOLTS
1 PT SUPPLY
T. BLOCK
MOLDED CASE SWITCH
1 PT. SUPPLY
MOLDED CASE CIRCUIT
BREAKER 1 PT. SUPPLY
INSTALLED
LUG
INSTALLED
LUG
ALTERNATE
LUG
INSTALLED
LUG
ALTERNATE
LUG
YLAA0081
208 (2) # 6–500 (2) 250–500 (3) 2/0–400 (3) 2/0–400 (2) 250–500
230 (2) # 6–500 (2) 250–500 (3) 2/0–400 (3) 2/0–400 (2) 250–500
380 (1) # 6–500 (1) 250–500 (2) 3/0–250 (2) 3/0–250 (1) 250–500
460 (1) # 6–500 (1) 250–500 (2) 3/0–250 (1) 6–350 —
575 (1) # 6–500 (1) 6–350 — (1) 6–350 —
YLAA0082
208 (2) # 6–500 (2) 250–500 (3) 2/0–400 (3) 2/0–400 (2) 250–500
230 (2) # 6–500 (2) 250–500 (3) 2/0–400 (3) 2/0–400 (2) 250–500
380 (1) # 6–500 (1) 250–500 (2) 3/0–250 (2) 3/0–250 (1) 250–500
460 (1) # 6–500 (1) 250–500 (2) 3/0–250 (1) 6–350 (1) 6–350
575 (1) # 6–500 (1) 6–350 — (1) 6–350 (1) 6–350
YLAA0089
208 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
230 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
380 (1) # 6–500 (2) 3/0–250 (1) 250–500 (2) 3/0–250 (1) 250–500
460 (1) # 6–500 (1) 250–500 (2) 3/0–250 (1) 6–350 —
575 (1) # 6–500 (1) 6–350 — (1) 6–350 —
YLAA0092
208 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
230 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
380 (1) # 6–500 (2) 3/0–250 (1) 250–500 (2) 3/0–250 (1) 250–500
460 (1) # 6–500 (1) 250–500 (2) 3/0–250 (1) 6–350 —
575 (1) # 6–500 (1) 6–350 — (1) 6–350 —
YLAA0100
YLAA0101
208 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
230 (2) # 6–500 (2) 250–500 (3) 2/0–400 (2) 250–500 (3) 2/0–400
380 (1) # 6–500 (2) 3/0–250 (1) 250–500 (2) 3/0–250 (1) 250–500
460 (1) # 6–500 (2) 3/0–250 (1) 250–500 (2) 3/0–250 (1) 250–500
575 (1) # 6–500 (1) 6–350 — (1) 6–350 —
TABLE 12 - WIRING LUGS (CONT’D)