Parameters relating to fans
Parameters relating to fans
Parameters Description Level VS Unit Max. Min. Value
F01
Fan outlet:
0= Absent (function not available)
1= Present
F 10 (R/W) 1 0 1
F02
Operating mode:
0=Always ON (function not available)
1= In parallel with compressor
2=ON/OFF operation (function not avail‐
able)
3= In parallel with the compressor and
speed regulation (function not available)
U 48 (R/W) 3 0 1
F03 Minimum Triac voltage F 49 (R/W) step F04 0 0
F04 Maximum Triac voltage F 50 (R/W) step 100 F03 100
F11 Fan start-up time F 51 (R/W) Seconds 120 0 0
F12 Triac impulse duration F 52 (R/W) Seconds 10 0 0