EasyManua.ls Logo

York YLCD Series - Page 39

York YLCD Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unit configuration parameters
Unit configuration parameters
Display Description Level VS Unit Max. Min. Value
H01
Unit model:
2= Water cooler
3= Air-water heat pump
F 54 (R/W) 3
H02
Number of ventilation circuits (do not modify this pa‐
rameter)
F 12 (R/W) 0
H03
No. of evaporating units present (do not modify this
parameter)
F 13 (R/W) 0
H04
No. of compressors per circuit (do not modify this pa‐
rameter)
F 55 (R/W) 2
H05
Pump operation:
0= Absent
1= Always ON
2= ON upon controller call
3= ON upon controller and time call
F 56 (R/W) 3 0 1
H06
COOL/HEAT digital input:
0= Absent
1= Present
U 14 (R/W) 1 0 0
H07
ON/OFF digital input:
0= Absent
1= Present
U 15 (R/W) 1 0 0
H08 Network configuration (do not modify this parameter) F 57 (R/W) 3 0 2
H09
Keyboard locked:
0= Disabled
1= Enabled
U 16 (R/W) 1 0 1
H10
Serial direction for monitoring:
0= Future use as terminal
U 58 (R/W) 200 1 1
H11 Output configuration (not selectable) F 59 (R/W) 3 0 0
H12
4-way valve logic operation. Activated in heat cycle.
(do not modify this parameter)
F 60 (R/W) 3 0 1
H22
Default parameter loading disabled:
0= Disabled
1= Enabled
F 18 (R/W) 1 0 1
H23
Modbus protocol setting:
0= Disabled
1= Enabled
F 11 1 0 0
User manual 1
Operating instructions 1.5
37

Related product manuals