TABLE 47 – VSD FAULT DEFINITIONS
Address
Short Name
(BACnet Object Name)
Fault Code Note
BAS Driver
1076 1101
bit15
1: Fault
bit14
bit13 Temp sensor fault 103
bit12
bit11 Current sensor checkout failure 105
bit10
bit9
bit8 Bus undervoltage fault 108
bit7 Bus overvoltage fault 109
bit6 Precharge fault 110
bit5 FOCx/APFCx over-temp fault 111
bit4 Current sensor fault 112
bit3 Open phase 113
bit2 Driver internal fault 114
bit1 Driving fault 115
bit0 FOCx/APFCx overcurrent fault 116