EasyManua.ls Logo

York ZJ Series - Weights and Dimensions; ZJ037-061 Unit Accessory Weights; Unit 4 Point Load Weight; Unit 6 Point Load Weight

York ZJ Series
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5565591-YIM-B-1019
8 Johnson Controls Ducted Systems
Figure 5: Unit 4 Point Load Weight
Figure 6: Unit 6 Point Load Weight
Figure 7: Center of Gravity
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
D
A
CB
LEFT
FRONT
D
A
C
B
E
F
LEFT
FRONT
X
Y
LEFT
FRONT
Table 2: Weights and Dimensions
Size
(Tons)
Model
Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
ShippingOperatingX Y ABCDABCDEF
037
(3)
ZJ 745 740 40 26 180 147 186 228 124 108 95 120 137 157
049
(4)
ZJ 767 762 40 24 171 139 203 249 118 102 90 131 149 172
061
(5)
ZJ 780 775 40 24 174 142 207 253 120 104 91 133 152 175
Table 3: ZJ037-061 Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping Operating
Economizer 90 85
Power Exhaust 40 35
Electric Heat
1
49 49
Gas Heat
2
110 110
1. Weight given is for the maximum heater size available (24KW).
2. Weight given is for the maximum number of tube heat exchangers
available (8 tube).