6
installing W1 or W2 module can implement TRIAC no contact switch output.
Alarm (ALM): Support 1 normally open + normally close relay output (AL1) by installing L0 or
L2 module or 2 normally open relay outputs (AL1+AL2) by installing L3 module.
Auxiliary output (AUX): Support 1 normally open + normally close relay output (AL1) by
installing L0 or L2 module or 2 normally open relay outputs (AL1+AL2) by installing L3 module. or
be used for communicating with computer by installing R module (RS232C interface).
Communication Interface (COMM): Module S or S4 can be installed in for communicating with
computer (RS485 communication interface), and it can also be used as power supply for external
sensor when equipped with a voltage output module (except for front panel D2 size).
1.3.2 Commonly used modules:
N No module installed (or null)
L0 Normally open + normally close relay output module (large volume, capacity: 30VDC/2A,
250VAC/2A,suitable for alarm)
L1 Normally open + normally close relay output module (large volume, capacity: 30VDC/2A,
250VAC/2A)
L2 Normally open + normally close relay output module (small volume, capacity: 30VDC/1A,
250VAC/1A,suitable for alarm)
L3 Dual normally open relay output module (Capacity: 30VDC/2A, 250VAC/2A)
L4 Large capacity normally open relay output module (large volume, Capacity: 30VDC/2A,
250VAC/2A) W1/W2 TRIAC no contact normally open (W2 is normally close) discrete
output module (Capacity:100-240VAC/0.2A)
G SSR voltage output module (DC12V/30mA)
G5 Dual SSR voltage driver (DC12V/30mA)
K1 Single-phase thyristor zero crossing trigger output module (can trigger one loop of a
TRIAC or a pair of inverse parallel SCR with current of 5-500A)
K3 Three-phase thyristor zero crossing trigger output module (can trigger 3-phase circuit;
each loop can trigger TRIAC or a pair of inverse parallel SCR with current of 5-500A)
K5/K6 Single-phase 220VAC/380VAC thyristor phase-shift trigger output module (can trigger one
loop of TRIAC or a pair of inverse parallel SCR with current of 5-500A), only 50Hz power
X3/X5 Linear current output module (continuous 0-22mA output, selectable in the range of
0-10mA, 4-20mA etc.).
X5 is equipped with photoelectric isolated power supply.
S/S4 RS485 communication interface module. S4 is equipped with photoelectric isolated power
supply.
R RS232 communication interface module.
I2 Switch / frequency signal input interface for inputting external switch or frequency signal,
has a 12VDC power supply for external transducer.
I4 4-20mA/0-20mA analogue input interface, has a 24VDC/24mA power supply for a
transmitter.
V24/V12/V10/U5
Isolated 24V/12V/10V/5V DC voltage output with maximum current of 50mA, can supply power for
transmitter.