2.2 Parameter Setting Flow Chart
2.3 Operation Description
2.3.1 Parameter Setting
In basic display status, press and hold for about 2 seconds can access Field Parameter Table.
Press can go to the next parameter; press 、 or can modify a parameter.
Press and hold can return to the previous parameter. Press (don't release) and then
press key simultaneously can escape from the parameter table. The instrument will escape
auomatically from the parameter table if no key is pressed within 25 seconds, and the change of the
last parameter will not be saved.
In Field Parameter Table, till the last field parameter Loc appears. Setting Loc=808 and then
press can access System Parameter Table.
2.3.2 Set Value Setting
In basal display status, if the parameter lock
“
Loc
”
isn't locked, we can set setpoint (SV) by
pressing first、