AF2ZP0CL - ACE2 - User Manual Page - 43/85
The contactor will be closed with 70% of battery voltage applied to the coil
and then the voltage will be reduced to 49% of battery voltage.
15) AUX OUTPUT V RID
It specifies the percentage of AUX OUT VOLT parameter, supplied to EB coil
to keep the electro mechanic brake applied.
Example 1
MAIN CONT VOLTAGE = 100%
MAIN CONT V RID = 70%
The load will be closed with full battery voltage applied to the coil and then
the voltage will be reduced to 70% of battery voltage.
Example 2
MAIN CONT VOLTAGE = 70%
MAIN CONT V RID = 100%
The load will be closed with 70% of battery voltage applied to the coil and
then the voltage will be kept at the same value.
Example 3
MAIN CONT VOLTAGE = 70%
MAIN CONT V RID = 70%
The load will be closed with 70% of battery voltage applied to the coil and
then the voltage will be reduced to 49% of battery voltage.