Options for speed setting for types FSDM22...50
0...10 V (factory setting)
Control via external setting signal 0...10 V
or
Speed setting by external potenziometer (10 kΩ) at terminals “+10 V” and “GND” pick of-off at terminal “E1”.
E1 D1 GND
0...10 V
+
Analog In 1
E1.1
V
E1 D1 GND 10V
Analog In 1
10 V DC Out
10 kΩ
13.06.2014
i_jumper_motor_mounted_0_10v.eps
0...100 % PWM (factory setting)
Control via external setting signal PWM
E1.1
PWM
E1 D1 GND 10V
Analog In 1
10 V DC Out
13.06.2014
i_jumper_motor_mounted_pwm.eps
24V
24 V DC Out
24 V
15...28 V
+
-
GND
E1
E1.1
PWM
(10 V)
E1 D1 GND 10V
Analog In 1
10 V DC Out
24V
24 V DC Out
PWM
f = 1...10 kHz
10 kΩ
0...20 mA
Control via external setting signal 0...20 mA
E1
D1 GND
0...20 mA
+
Analog In 1
E1.1
mA
13.06.2014
i_jumper_motor_mounted_0_20ma.eps
5.9 Output voltage “10 V”
Voltage supply e.g. for speed setting by external potentiometer.
Connection: “10 V” - “GND” (max. load see Technical data und connection diagram).
•
It is not permissible to connect voltage outputs of several devices to each other!
•
It is not permissible to connect voltage outputs in the device to each other!
Operating Instructions Fcontrol Basic – model series FSDM2.5..50M Electrical installation