Page 12 of 20 804050UK G4 Commercial chilled and sparkling installation instructions - Sept. 2016 - v3.02
Ventilation
1.3 Alternative arrangement (Dual fan kit)
In situations where the preferred arrangement cannot be used or will not work effectively e.g.
• Single cupboard where the 100mm grille spacing cannot be achieved.
• Where there are openings in the back of the cupboard allowing exhaust air to recirculate into the cupboard
space.
An SP93156 Dual exhaust fan kit* must be fitted in either arrangement A or B shown below and connected to
the DIN socket on the Command-Centre
TM
.
A Fan kit fitted to kick board and with kick space duct fitted to the Command-Centre
TM
.
B Fan kit fitted to cupboard door (position B1) or side (position B2) and without kick space duct fitted
to the Command-Centre
TM
.
*
For dual exhaust fan cut-out dimensions see the instructions provided with the kit.
B1
B2
A B
1.4 Alternative arrangement (Vent tray)
In situations where cupboard width is 1000mm or greater, without central pillar and where vent grilles cannot
be fitted in the kick board (e.g. hospitals) use a Vent tray kit (CS SP93541).
Vent tray
100mm
min.
A vent grille, supplied should be used as an inlet vent and fitted to the cabinet side (adjacent to the
Command-Centre air inlet) as shown below. It must take in air from the room or another ventilated space.
This space could be an adjacent cupboard, (via a communicating port) on condition that it does not contain
a heat generating appliance. The vent grille or the angled inlet grille supplied should be fitted in the adjacent
cupboard,
observing 100mm
separation from
the vent tray
exhaust.