Address Modbus register Name Scaling Type
1
30001,30001
FB Status word
-
Binary
44 30044,40044 FB Setpoint speed 0.1 Hz
48 30048,40048 Password - Binary
49
30049,40049
Password
-
Binary
EBM
EBM frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read from the frequency converter:
Address Modbus register Name Scaling Type
27 30027,40027 FB Status word - Binary
511 3051140511 Cumulative output 0.1 kWh
527
30527,40527
Motor frequency
0.1
+/- Hz
508 30508,40508 Motor current 0.1 A
510 30510,40510 Motor output 0.01 kW
505
30505,40505
DC voltage
1
V
30 30030,40030 Active error - Error code
The following signals can be used to control fan speed:
Address Modbus register Name Scaling Type
1 30001,30001 Control Word - Binary
44 30044,40044 FB Setpoint speed 0.1 Hz
48 30048,40048 Password - Binary
49 30049,40049 Password - Binary
Danfoss FC 101
Danfoss frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read from the frequency converter:
Address Modbus register Name Scaling Type
27 30027,40027 FB Status word - Binary
511
3051140511
Cumulative output
0.1
kWh
527 30527,40527 Motor frequency 0.1 +/- Hz
508 30508,40508 Motor current 0.1 A
510 30510,40510 Motor output 0.01 kW
505
30505,40505
DC voltage
1
V
30 30030,40030 Active error - Error code