86 Chapter 17 Configuration Manual Corrigo Ventilation, revision R
17.11 Pump control
P1-Heating
P1-Exchanger
P1-Cooling
In these menus the parameters for pump control are set.
If, for any of the control circuits, no output is configured for pump control these settings will be
ignored.
P1 Heating
Pump stop: Yes
Stop delay: 5 min
Outd. Temp stop: 10°C
Differential: 1.0°C
P1 Exchanger
P1-Exchanger
Stop delay: 5 min
P1 Cooling
P1-Cooling
Stop delay: 5 min
For a detailed description of pump functions, see the section Pump control.
17.12 Free cooling
Free cool active:Yes
Outd. temp activation
22.0°C
Outd. Temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
Free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 min
Fan output
when free cooling
SAF: 0 %
EAF: 0 %