EasyManua.ls Logo

AB Regin Corrigo E81D-3 - System

AB Regin Corrigo E81D-3
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
102 Chapter 17 Configuration Manual Corrigo Ventilation, revision R
Automatically
restart after
power on:
Yes
17.31 System
17.31.1 Change language
Use this menu to change the display language.
Choose language
English
Note, this menu is also directly accessible by holding the OK-button depressed during power-up or
by pressing right arrow three times when the start display is shown.
The different language files are stored in the application memory and are downloaded to the work
memory. If a Corrigo via E tool
©
has been reloaded with a newer program revision than the factory
revision, the controller will not allow language files to be downloaded from the application
memory. This is because there is a risk that the language files are not compatible with the new
revision. Therefore, you are limited to the two languages you have downloaded using E tool
©
.
17.31.2 Choose start display, the text normally shown on the
display
There are five different to choose from.
Type 1
The text on the first line can be changed using E tool
©
.
The second line shows the date and time.
The third line shows the present running status.
The fourth line shows the present temperature setpoint and actual values.
Vent unit 18 PX
2004-08-15 11:28
System: Running
Sp:22.0°C Act:21.8°C
Type 2
The first line shows the date and time.
The second line shows the present running status.
The third line shows the present temperature setpoint and actual values.
The fourth line shows the present temperature control output values.
2004-08-15 11:28
System: Running
Sp:22.0°C Act:21.8°C
Y1:0% Y2:93% Y3:0%
Type 3
The first line shows the date and time.

Table of Contents