Manual Corrigo Ventilation, revision R Chapter 15 Settings 75
Alarm limit, pressure
Control dev SAF
40.0 Pa
Control dev EAF
40.0 Pa
Alarm limit Humidity
Control deviation
humidity
10 %
Alarm limit, exchanger efficiency
Low efficiency
50.0 %
Service alarm filter
Service alarm
(Filter alarm)
Time until alarm
Activates: 0 month
15.6.2 Alarm delays
Alarm delay, supply air
Al. del. supply air
Control dev: 30 min
High temp: 5 sec
Low temp: 5 sec
Alarm delay, extract air
Al. del. extract air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, room
Al. del. room air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, frost protection
Alarm delay
Frost prot.: 0 sec
Frost risk: 0 sec
Alarm delay control SAF and EAF
Alarm delay control
dev. pressure
SAF: 30 min
EAF: 30 min
Alarm delay, Humidity
Alarm delay control
deviation humidity 30
Min