Chapter 2 Overview of ACH 400 with Electronic Bypass
ACH 400 with Electronic Bypass Users Manual 2-3
Table 2-1 Drive Input Fuse Rating
Note: Fuses listed are similar in function to fuses listed in the ACH 400
Users Manual, physical characteristics may differ. Fuses from other
manufacturers can be used if they meet the ratings given in the table.
The fuses recommended in the table are UL recognized.
Line Reactor The ACH 400 Electronic Bypass may contain optional line reactors to provide
an additional 2% input impedance to limit the harmonics back to the power
line. This impedance is in addition to the approximately 3% input impedance
provided by internal reactors that are standard in the drive.
240 Volt Models 480 Volt Models
Frame
Drive Input
Fuse Ratings
(Semiconductor Protection)
Type Codes HP Type Codes HP
Amps
(660 V)
Bussmann
Type
ACH401x0043x 3
R1
10 KTK-R-10
ACH401x0053x 5 15 KTK-R-15
ACH401x0042x 3 15 KTK-R-15
ACH401x0063x 7.5 15 KTK-R-15
ACH401x0052x 5 25 KTK-R-25
ACH401x0093x 10
R2
20 KTK-R-20
ACH401x0062x 7.5 30 KTK-R-30
ACH401x0113x 15 30 KTK-R-30
ACH401x0163x 20
R3
40 JJS-40
ACH401x0203x 25 50 JJS-50
ACH401x0112x 10/15 60 JJS-60
ACH401x0162x 20 80 JJS-80
ACH401x0202x 25
R4
100 JJS-100
ACH401x0253x 30 60 JJS-60
ACH401x0303x 40 80 JJS-80
ACH401x0413x 50 100 JJS-100
ACH401x0302x 30 110 JJS-110
ACH401x0412x 40 150 JJS-150
ACH40160603x 60 R5 125 170M1368
ACH40160703x 75
R6
160 170M1369
ACH40160601x 50 400 170M2621
ACH40161003x 100 200 170M1370
ACH40160701x 60 400 170M2621
ACH40x61203x 125
R7
400 170M3169
ACH40x61403x 150 400 170M3169
ACH40262103x 200
R8
550 170M5161
ACH40262603x 250 700 170M5013
ACH40263203x 300
R9
700 170M5013
ACH40264003x 400 800 170M6012

Table of Contents