66 ACH550 Installation, Operation and Maintenance Manual
ACH550 E-Clipse Bypass
Note: In the Parameter Edit mode the current parameter value appears below the 
parameter name.
Note: To view the default parameter value, press the Up/Down arrows 
simultaneously. Press Enter to restore the default parameter value or press ESC to 
leave the Parameter Edit mode.
Diagnostics
Fault listing
9 Press ESC to return to the Default 
Display from the Main Menu.
Fault 
Code
Fault Name In 
Panel
Fault Possible Cause Corrective Action
3001 COIL CURR FBK RBCU is sensing 
abnormal current 
feedback when neither 
contactor should be 
energized
Defective component 
on RBCU
Change RBCU
3002 BYP CNTACT 
STUCK
M2 contactor indicates 
it is not prepared to 
move on a power up 
check of the contactor 
or after contact is 
commanded to open
Defective Contactor
Defective RBCU
Disconnect incoming 
power from unit
Check if contactor 
armature moves freely. 
If armature moves 
freely, then change the 
RBCU. If armature 
does not move freely, 
then change individual 
contactor (M2) or the 
complete assembly 
(RCSA-0x)
3003 DRV CNTACT 
STUCK
M1 contactor indicates 
it is not prepared to 
move on a power up 
check of the contactor 
or after contact is 
commanded to open
Defective Contactor
Defective RBCU
Disconnect incoming 
power from unit
Check if contactor 
armature moves freely. 
If armature moves 
freely, then change the 
RBCU. If armature 
does not move freely, 
then change individual 
contactor (M1) or the 
complete assembly 
(RCSA-0x)