ACH550 Installation, Operation and Maintenance Manual 71
ACH550 E-Clipse Bypass
Fault History
See page 28.
3102 PMAP FILE Parameter file is
corrupt
Cycle Power
Contact ABB with
information that
preceeded fault
3201 T1 OVERLOAD T1 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3202 T2 OVERLOAD T2 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3203 T3 OVERLOAD T3 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3204 STACK
OVERFLOW
Program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3205 UNKNOWN CB Bypass control board
type is unknown.
Firmware is not
compatible with control
board in RBCU.
Firmware 93F and
greater compatible with
all RCBU hardware.
Firmware 93D and
earlier can only be
loaded in RBCU Rev D
and earlier.
3206 UNKNOWN DRIVE Drive reports rating not
found in bypass
software
Drive does not match
drives configured in
bypass RBCU
Replace RBCU or
reload with most
current firmware
3207 UNKNOWN
BYPASS
NA NA Replace RBCU or load
most current firmware
Contact ABB at
1-800-HELP-365
option 4
Replace RBCU or load
most current firmware
Fault
Code
Fault Name In
Panel
Fault Possible Cause Corrective Action