ACH550-UH User’s Manual 1-109
Parameters
1605 USER PAR SET CHG -6…6 1 0 (NOT SEL)
Defines control for changing the user parameter set.
• See parameter 9902 APPLIC MACRO.
• The drive must be stopped to change User Parameter Sets.
• During a change, the drive will not start.
Note: Always save the User Parameter Set after changing any parameter settings, or performing a motor
identification.
• Whenever the power is cycled, or parameter 9902
APPLIC MACRO is changed, the drive loads the last settings
saved. Any unsaved changes to a user parameter set are lost.
Note: The value of this parameter (1605) is not included in the User Parameter Sets, and it does not change if User
Parameter Sets change.
Note: You can use a relay output to supervise the selection of User Parameter Set 2.
• See parameter 1401.
0 =
NOT SEL – Defines the control panel (using parameter 9902) as the only control for changing User Parameter
Sets.
1 = DI1 – Defines digital input DI1 as a control for changing User Parameter Sets.
• The drive loads User Parameter Set 1 on the falling edge of the digital input.
• The drive loads User Parameter Set 2 on the rising edge of the digital input.
• The User Parameter Set changes only when the drive is stopped.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as a control for changing User Parameter Sets.
•See
DI1 above.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as a control for changing User Parameter Sets.
• The drive loads User Parameter Set 1 on the rising edge of the digital input.
• The drive loads User Parameter Set 2 on the falling edge of the digital input.
• The User Parameter Set changes only when the drive is stopped.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as a control for changing User Parameter
Sets.
•See DI1(INV) above.
1606 LOCAL LOCK -6…8 1 0 (
NOT SEL)
Defines control for the use of the HAND mode. The HAND mode allows drive control from the control panel.
• When LOCAL LOCK is active, the control panel cannot change to HAND mode.
0 =
NOT SEL – Disables the lock. The control panel can select HAND and control the drive.
1 =
DI1 – Defines digital input DI1 as the control for setting the local lock.
• Activating the digital input locks out local control.
• De-activating the digital input enable the HAND selection.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for setting the local lock.
•See
DI1 above.
7 =
ON – Sets the lock. The control panel cannot select HAND and cannot control the drive.
8 =
COMM – Defines bit 14 of the Command Word 1 as the control for setting the local lock.
• The Command Word is supplied through fieldbus communication.
• The Command Word is 0301.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for setting the local lock.
• De-activating the digital input locks out local control.
• Activating the digital input enable the HAND selection.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for setting the local lock.
•See
DI1(INV) above.
1607 PARAM. SAVE 0, 1 1 0 (
DONE)
Saves all altered parameters to permanent memory.
• Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use
this parameter.
• If 1602 PARAMETER LOCK = 2 (NOT SAVED), parameters altered from the control panel are not saved. To save, you
must use this parameter.
• If 1602
PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to
permanent memory.
0 =
DONE – Value changes automatically when all parameters are saved.
1 =
SAVE… – Saves altered parameters to permanent memory.
Group 16: System Controls
Code Description Range Resolution Default S