ACH550-UH User’s Manual 1-115
Parameters
Group 20: LIMITS
This group defines minimum and maximum limits to follow in driving the motor –
speed, frequency, current, torque, etc.
Group 20: Limits
Code Description Range Resolution Default S
2001 MINIMUM SPEED -30000…30000 rpm 1 rpm 0 rpm
Defines the minimum speed (rpm) allowed.
A positive (or zero) minimum speed value defines two ranges,
one positive and one negative.
A negative minimum speed value defines one speed range.
See the figure.
2002 MAXIMUM SPEED 0…30000 rpm 1 rpm 1800 (US)
Defines the maximum speed (rpm) allowed.
2003 MAX CURRENT 0.0… 1.3 • I
2n
0.1 A 1.3 • I
2n
Defines the maximum output current (A) supplied by the drive to the motor.
2006 UNDERVOLT CTRL 0…2 1 1 [ENABLE (TIME)]
Sets the DC undervoltage controller on or off. When on:
If the DC bus voltage drops due to loss of input power, the undervoltage controller decreases the motor speed in
order to keep the DC bus voltage above the lower limit.
When the motor speed decreases, the inertia of the load causes regeneration back into the drive, keeping the DC
bus charged and preventing an undervoltage trip.
The DC undervoltage controller increases power loss ride-through on systems with a high inertia, such as a
centrifuge or a fan.
0 =
DISABLE – Disables controller.
1 =
ENABLE(TIME) – Enables controller with 500 ms time limit for operation.
2 =
ENABLE – Enables controller without maximum time limit for operation.