ACH550-UH User’s Manual 1-121
Parameters
2205 ACCELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
Sets the acceleration time for zero to maximum frequency for ramp pair 2.
• See 2202 ACCELER TIME 1.
• Used also as jogging acceleration time. See 1004
JOGGING SEL.
2206 DECELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
Sets the deceleration time for maximum frequency to zero for ramp pair 2.
• See 2203
DECELER TIME 1.
• Used also as jogging deceleration time. See 1004
JOGGING SEL.
2207 RAMP SHAPE 2 0.0…1000.0 s 0.1 s 0.0 s
Selects the shape of the acceleration/deceleration ramp for ramp pair 2.
• See 2204
RAMP SHAPE 1.
2208 EMERG DEC TIME 0.0…1800.0 s 0.1 s 1.0 s
Sets the deceleration time for maximum frequency to zero for an emergency.
• See parameter 2109
EMERG STOP SEL.
• Ramp is linear.
2209 RAMP INPUT 0 -6…7 1 0 (
NOT SEL)
Defines control for forcing the speed to 0 with the currently used deceleration ramp (see parameters 2203
DECELER
TIME 1 and 2206 DECELER TIME 2).
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the speed to 0.
• Activating the digital input forces the speed to zero, after which the speed will stay at 0.
• De-activating the digital input: speed control resumes normal operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for forcing the speed to 0.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines inverted digital input DI1 as the control for forcing the speed to 0.
• De-activating the digital input forces the speed to 0.
• Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1(INV) above.
Group 22: Accel/Decel
Code Description Range Resolution Default S