ACH550-UH User’s Manual 1-127
Parameters
Group 29: MAINTENANCE TRIG
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Group 29: Maintenance Trig
Code Description Range Resolution Default S
2901 COOLING FAN TRIG 0.0…6553.5 kh 0.1 kh 0.0 kh
0.0 disables
Sets the trigger point for the drive’s cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902 COOLING FAN ACT 0.0…6553.5 kh 0.1 kh 0.0 kh
Defines the actual value of the drive’s cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2903 REVOLUTION TRIG 0…65535 Mrev 1 Mrev 0 Mrev
0 disables
Sets the trigger point for the motor’s accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904 REVOLUTION ACT 0…65535 Mrev 1 Mrev 0 Mrev
Defines the actual value of the motor’s accumulated revolutions counter.
• When parameter 2903 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 – Resets the parameter.
2905 RUN TIME TRIG 0.0…6553.5 kh 0.1 kh 0.0 kh
0.0 disables
Sets the trigger point for the drive’s run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906 RUN TIME ACT 0.0…6553.5 kh 0.1 kh 0.0 kh
Defines the actual value of the drive’s run time counter.
• When parameter 2905 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2907 USER MWh TRIG 0.0…6553.5 MWh 0.1 MWh 0.0 MWh
0.0 disables
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
• Value is compared to parameter 2908 value.
0.0 – Disables the trigger.
2908 USER MWh ACT 0.0…6553.5 MWh 0.1 MWh 0.0 MWh
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
• When parameter 2907 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.