ACH550-UH User’s Manual 1-145
Parameters
3610 START TIME 3 00:00:00…23:59:58 2 s 12:00:00 AM
Defines timer 3 daily start time.
• See parameter 3602.
3611 STOP TIME 3 00:00:00…23:59:58 2 s 12:00:00 AM
Defines timer 3 daily stop time.
• See parameter 3603.
3612 START DAY 3 1…7 1 1 (
MONDAY)
Defines timer 3 weekly start day.
• See parameter 3604.
3613 STOP DAY 3 1…7 1 1 (
MONDAY)
Defines timer 3 weekly stop day.
• See parameter 3605.
3614 START TIME 4 00:00:00…23:59:58 2 s 12:00:00 AM
Defines timer 4 daily start time.
• See parameter 3602.
3615 STOP TIME 4 00:00:00…23:59:58 2 s 12:00:00 AM
Defines timer 4 daily stop time.
• See parameter 3603.
3616 START DAY 4 1…7 1 1 (
MONDAY)
Defines timer 4 weekly start day.
• See parameter 3604.
3617 STOP DAY 4 1…7 1 1 (
MONDAY)
Defines timer 4 weekly stop day.
• See parameter 3605.
3622 BOOSTER SEL -6…6 1 0 (
NOT SEL)
Selects the source for the booster signal.
0 =
NOT SEL – Booster signal is disabled.
1 =
DI1 – Defines DI1 as the booster signal.
2…6 =
DI2…DI6 – Defines DI2…DI6 as the booster signal.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the booster signal.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the booster signal.
3623 BOOSTER TIME 00:00:00…23:59:58 2 s 00:00:00
Defines the booster ON time. Time is started when booster sel
signal is released. If parameter value is 01:30:00, booster is
active for 1 hour and 30 minutes after activation DI is
released.
Group 36: Timed Functions
Code Description Range Resolution Default S
Booster active
Activation DI
Booster time