1-14 ACH550-UH User’s Manual
Installation
For flange mounting (mounting the drive in a cooling air duct), see the appropriate
Flange Mounting Instructions:
Prepare the mounting location
The ACH550 should only be mounted where all of the
requirements defined in Preparing for installation on
page 1-10 are met.
1. Mark the position of the mounting holes.
Note: Frame sizes R3 and R4 have four holes along the top. Use only two. If
possible, use the two outside holes (to allow room to remove the fan for
maintenance).
Note: ACH400 drives can be replaced using the original mounting holes. For R1 and
R2 frame sizes, the mounting holes are identical. For R3 and R4 frame sizes, the
inside mounting holes on the top of ACH550 drives match ACH400 mounts.
Frame size
IP21 / UL type 1 IP54 / UL type 12
Kit Code (English) Kit Code (English)
R1 FMK-A-R1 100000982 FMK-B-R1 100000990
R2 FMK-A-R2 100000984 FMK-B-R2 100000992
R3 FMK-A-R3 100000986 FMK-B-R3 100000994
R4 FMK-A-R4 100000988 FMK-B-R4 100000996
R5 AC8-FLNGMT-R5 ACS800-PNTG01U-EN - -
R6 AC8-FLNGMT-R6 - -