ACH550-UH User’s Manual 1-177
Parameters
8120 INTERLOCKS 0…6 1 4 (DI4)
Defines operation of the Interlock function. When the Interlock function is enabled:
An interlock is active when its command signal is absent.
An interlock is inactive when its command signal is present.
The ACH550 will not start if a start command occurs when the speed regulated motor’s interlock is active – the
control panel displays an alarm (2015,
PFA I LOCK).
Wire each Interlock circuit as follows:
Wire a contact of the motor’s On/Off switch to the Interlock circuit – the drive’s PFA logic can then recognize that
the motor is switched off and start the next available motor.
Wire a contact of the motor thermal relay (or other protective device in the motor circuit) to the Interlock input – the
drive’s PFA logic can then recognize that a motor fault is activated and stop the motor.
0 =
NOT SEL – Disables the Interlock function. All digital inputs are available for other purposes.
Requires 8118
AUTOCHNG INTERV = 0.0 (The Autochange function must be disabled if Interlock function is
disabled.)
1 =
DI1 – Enables the Interlock function and assigns a digital input (starting with DI1) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (PFA)]
the Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0.0, and otherwise enabled).
Group 81: PFA Control
Code Description Range Resolution Default S
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1: Speed Reg Motor
DI2…DI6: Free
Not allowed
1
DI1: Speed Reg Motor
DI2: First PFA Relay
DI3…DI6: Free
DI1: First PFA Relay
DI2…DI6: Free
2
DI1: Speed Reg Motor
DI2: First PFA Relay
DI3: Second PFA Relay
DI4…DI6: Free
DI1: First PFA Relay
DI2: Second PFA Relay
DI3…DI6: Free
3
DI1: Speed Reg Motor
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5…DI6: Free
DI1: First PFA Relay
DI2: Second PFA Relay
DI3: Third PFA Relay
DI4…DI6: Free
4
DI1: Speed Reg Motor
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5: Fourth PFA Relay
DI6: Free
DI1: First PFA Relay
DI2: Second PFA Relay
DI3: Third PFA Relay
DI4: Fourth PFA Relay
DI5…DI6: Free
5
DI1: Speed Reg Motor
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5: Fourth PFA Relay
DI6: Fifth PFA Relay
DI1: First PFA Relay
DI2: Second PFA Relay
DI3: Third PFA Relay
DI4: Fourth PFA Relay
DI5: Fifth PFA Relay
DI6: Free
6 Not allowed
DI1: First PFA Relay
DI2: Second PFA Relay
DI3: Third PFA Relay
DI4: Fourth PFA Relay
DI5: Fifth PFA Relay
DI6: Sixth PFA Relay