EasyManua.ls Logo

ABB ACH550-VCR - Page 210

ABB ACH550-VCR
642 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-206 ACH550-UH User’s Manual
Embedded fieldbus
Change of State (COS) enabled
Alarm Enabled
Warning Enabled
Override value is received, but there is no action taken.
Binary Input – The binary input objects support the following features:
Binary Input actual value
Normal / Alarm state specification
Alarm Enabled
Change of State (COS) enabled
Override value is received, but there is no action taken.
Analog Output – The analog output objects support the following features:
Analog Output value in engineering units
Override value is used to change the Analog Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
Binary Output – The binary output objects support the following features:
Binary Output value
Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
Metasys integration
The following diagram shows the drives’ integration to the Johnson Controls
Metasys system.
N1LAN
NCU
N2 Fieldbus

Table of Contents

Other manuals for ABB ACH550-VCR

Related product manuals