ACH550-UH User’s Manual 1-229
Embedded fieldbus
BV8 AT SETPOINT This object indicates whether
the drive is at the
commanded setpoint.
YES/NO R
BV9 ENABLE ACT This object indicates the
System Enable command
status (the combination of all
Run and Start Enables),
regardless of the control
source.
ENABLE/
DISABLE
R
BV10 RUN/STOP CMD This object commands a drive
start. Control requires either:
• Parameter 1001 value =
COMM for control by EXT1
or
• Parameter 1002 value =
COMM for control by EXT2.
RUN/STOP C
BV11 FWD/REV CMD This object commands a
motor rotation direction
change. Control requires
1003 =
REQUEST and either:
• Parameter 1001 value =
COMM for control by EXT1
or
• Parameter 1002 value =
COMM for control by EXT2.
REV/FWD C
BV12 RUN ENA CMD This object commands Run
Enable. Control requires
parameter 1601 value =
COMM.
ENABLE/
DISABLE
C
BV13 EXT 1/2 CMD This object selects ext1 or
ext2 as the active control
source. Control requires
parameter 1102 value =
COMM.
EXT2/EXT1 C
BV14 FAULT RESET This object resets a faulted
drive. The command is rising-
edge triggered. Control
requires parameter 1604
value =
COMM.
RESET/NO C
BV15 MBOX READ This object reads a parameter
(defined by AV25
MBOX
PARAM) and returns it in AV26
MBOX DATA.
READ/RESET W
BV16 MBOX WRITE This object writes the data
value specified by AV26,
MBOX DATA, to a parameter
(defined by AV25,
MBOX
PARAM).
WRITE/RESET W
BV17 LOCK PANEL This object locks the panel
and prevents parameter
changes. The corresponding
drive parameter is 1602.
LOCK/UNLOCK W
Instance
ID
Object Name Description
Active/Inactive
Text
Present Value
Access Type