EasyManua.ls Logo

ABB ACH550-VCR - Page 265

ABB ACH550-VCR
642 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACH550-UH User’s Manual 1-261
Fieldbus adapter
The serial communication channel is defined as the source for controlling
commands from EXT1 (set using parameters 1001 EXT1 COMMANDS and 1102
EXT1/EXT2 SEL).
The external plug-in fieldbus adapter is activated:
Parameter 9802 COMM PROT SEL = 4 (EXT FBA).
The external plug-in fieldbus adapter is configured to use the drive profile
mode or drive profile objects.
The content of the
CONTROL WORD depends on the protocol/profile used. See the
users manual provided with the FBA module and/or the ABB drives profile technical
data.
Status Word
The
STATUS WORD is a 16-bit word containing status information, sent by the drive to
the fieldbus controller. The content of the
STATUS WORD depends on the protocol/
profile used. See the users manual provided with the FBA module and/or the ABB
drives profile technical data section.
Reference
The contents of each
REFERENCE word:
Can be used, as speed or frequency reference.
Is a 16-bit word comprised of a sign bit and a 15-bit integer.
Negative references (indicating reversed rotation direction) are indicated by the
two’s complement of the corresponding positive reference value.
The use of a second reference (REF2) is supported only when a protocol is
configured for the ABB Drives profile.
Reference scaling is fieldbus type specific. See the user’s manual provided with the
FBA module and/or the following sections as appropriate:
ABB drives profile technical data
Generic profile technical data
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example, group 01 parameters) can be mapped to
Input Words using group 51 parameters (protocol-dependent, but typically
parameters 5104…5126).
Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
What control information must be sent down to the drives?
What feedback information must be sent from the drives to the controlling
system?

Table of Contents

Other manuals for ABB ACH550-VCR

Related product manuals