1-284 ACH550-UH User’s Manual
Diagnostics
201 DSP T1
OVERLOAD
Error in the system. Contact your local ABB sales representative and report
the error number.
202 DSP T2
OVERLOAD
203 DSP T3
OVERLOAD
204 DSP STACK
ERROR
205
RESERVED
(obsolete)
206 OMIO ID ERROR
207
EFB LOAD ERR
1000 PAR HZRPM
LIMITS
Parameter values are inconsistent. Check for any of the following:
2001
MINIMUM SPEED > 2002 MAXIMUM SPEED.
2007 MINIMUM FREQ > 2008 MAXIMUM FREQ.
2001
MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range
(> 50)
2002
MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range
(> 50)
2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50)
2008
MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50)
1001
PAR PFAREFNG Parameter values are inconsistent. Check for the following:
2007
MINIMUM FREQ is negative, when 8123 PFA ENABLE is active.
1002 RESERVED
(Obsolete)
1003
PAR AI SCALE Parameter values are inconsistent. Check for any of the following:
1301
AI 1 MIN > 1302 AI 1 MAX.
1304 AI 2 MIN > 1305 AI 2 MAX.
1004 PAR AO SCALE Parameter values are inconsistent. Check for any of the following:
1504
AO 1 MIN > 1505 AO 1 MAX.
1510
AO 2 MIN > 1511 AO 2 MAX.
1005 PAR PCU 2 Parameter values for power control are inconsistent: Improper motor
nominal kVA or motor nominal power. Check for the following:
1.1 <
(9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / P
N
) < 3.0
•Where: P
N
= 1000 * 9909 MOTOR NOM POWER (if units are kW)
or P
N
= 746 * 9909 MOTOR NOM POWER (if units are HP, e.g. in US)
1006
EXT ROMISSING Parameter values are inconsistent. Check for the following:
Extension relay module not connected and
1410…1412
RELAY OUTPUTS 4…6 have non-zero values.
1007 PAR
FBUSMISSING
Parameter values are inconsistent. Check for and correct:
A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 10
(
COMM)), but 9802 COMM PROT SEL = 0.
1008
PAR
PFAWOSCALAR
Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3
(
SCALAR: SPEED), when 8123 PFA ENABLE is activated.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action