ACH550 E-Clipse Bypass User’s Manual 2-57
Application macros
Smoke Control (Override1) macro
* Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in
Automatic Smoke Control mode. Refer to the Smoke Control (Override1) documentation.
Parameter Number Description Setting
1602 Damper End Switch
RUN ENABLE (Run Permissive)
DI2
1603 High Pressure Switch, High Priority Safties
START EN 1 (Safety Interlock 1)
DI3
1604 Supply Smoke Detector, Emergency Shutdown
START EN 2 (Saftey Interlock 2)
DI4
1605 Freezestat, Low Priority Safties
START EN 3 (Saftey Interlock 2)
DI5