ACH550 E-Clipse Bypass User’s Manual 2-65
Parameters
Group 05: Event Log
0413 F2 VOLTAGE 1V 0 - 1200V 0 Input voltage at 2nd to last fault
0414 F2
CURRENT
0.1A 0.0 - 6553.5A 0 Motor current at 2nd to last fault
0415 F2 EVENT 1 See parameter 501 0 Last event status before 2nd to
last fault
0416 F2 E1 TIME 2, before 00:00:00 - 23:59:58 0 Time before 2nd last fault of last
event: hr:min:sec if time < 1 day
1, days
before
0 - 9999 days if time >= 1 day
0417 F2 EVENT 2 See parameter 501 0 2nd to last event before 2nd to
last fault
0418 F2 E2 TIME 2, before 00:00:00 - 23:59:58 0 Time before 2nd last fault of 2nd
last event: hr:min:sec if time < 1
day
1, days
before
0 - 9999 days if time >= 1 day
0419 FAULT 3 1 3001 - 3999
See 'Faults' page
0 3rd to last fault
0420 FAULT 4 1 3001 - 3999
See 'Faults' page
0 4th to last fault
0421 FAULT 5 1 3001 - 3999
See 'Faults' page
0 5th to last fault
Group 05: Event Log
Code Name Resolution Range Default Description
0501 LAST EVENT b0: 1 = Bypass mode
b1: 1 = Safeties In
b2: 1 = Run Enable
b3: 1 = Start
b4: 1 = In Auto Transfer
b5: 1 = Override 2
b6: 1 = Override 1
b7: 1 = Drive Fault
b8: 1 = Bypass Fault
b9: 1 = System Started
b10: 1 = System Running
b11:1 = Drive First Start
Completed
b12: not used
b13: not used
b15,b14: 0,0 = Off; 0,1 =
Hand, 1,0 = Auto; 1,1 = not
valid
0 Status at last event
0502 E1 TIME 1 1, days ago 0 - 65535 0 Time since last event, days
Group 04: Fault Log
Code Name Resolution Range Default Description