2-88 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
5304 EFB PARITY
Defines the data length,
parity and stop bits to be
used with the EIA 485 link
communication.
The same settings must
be used in all on-line
stations.
0 = 8
N1 – 8 data bits, No
parity, one stop bit.
1 = 8N2 – 8 data bits, No
parity, two stop bits.
2 = 8E1 – 8 data bits, Even
parity, one stop bit.
3 = 8
O1 – 8 data bits, Odd
parity, one stop bit.
Default: 1 Default: 0
5305 EFB CTRL PROFILE
Selects the communication
profile used by the EFB
protocol.
0 =
ABB DRV LIM
Operation of Control/
Status Words conform to
limited ABB Drives
Profile, as used in
ACH400/550.
1 =
DCU PROFILE
Operation of Control/
Status Words conform to
32-bit DCU Profile.
2 =
ABB DRV FULL
Operation of Control/
Status Words conform to
ABB Bypass Profile, as
used in ACS600/800.
Default: 0 Default: 0
5310 DV PAR10
Sets the response
turnaround time in
milliseconds.
Not used
for Comm
setup.
When this protocol is selected, the default
value is:
3 ms 0 ms 5 ms
Bypass
Parameter
Description
EFB Protocol Reference
Modbus N2 FLN BACnet