ACH550 E-Clipse Bypass User’s Manual 2-93
Embedded fieldbus
Start/stop control (Drive only)
Using the fieldbus for start/stop control of the drive only requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Control commands must be addressed to the Drive node with parameter 1625 set
to 0 (
DRIVE ONLY). For SYSTEM control refer to Start/stop control (System) on
page 2-100.
1. For Modbus, the protocol reference can depend on the profile used, hence two columns in these
tables. One column refers to the ABB Drives profile, selected when parameter 5305 = 0 (
ABB DRV
LIM) or 5305 = 2 (ABB DRV FULL). The other column refers to the DCU profile selected when
parameter 5305 = 1 (
DCU PROFILE). See ABB control profiles technical data – drive section on page
2-182.
Bypass
Parameter
Value Description
Protocol Reference
Modbus
1
N2 FLN BACnet
ABB DRV
DCU
PROFILE
1601 START/
S
TOP
2 (COMM) Start/Stop by
fieldbus with Ext1
or Ext2 selected.
40001
bits 0…3
40031
bits 0, 1
BO1 24 BV10
1625
COMM
CTRL
0 (DRIVE
ONLY)
Enable drive only
control.
N/A