2-102 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
Bypass relay output control
Using the fieldbus for relay output control requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
For example: To control relays 1 and 2 using serial communication:
From the bypass keypad, set parameters 1401
RELAY OUTPUT 1 and 1402 RELAY
OUTPUT 2 = 16 (COMM CTRL).
Then, for example using N2:
To turn Relay 1 On: Force object BO5 to On.
To turn Relay 2 On: Force object BO6 to On.
To turn both Relay 1 and 2 On: Force objects BO5 and BO6 On.
Note: Relay status feedback occurs without configuration as defined below.
Bypass
Parameter
Value Setting
Protocol Reference
Modbus N2 FLN BACnet
1401 RELAY
OUTPUT 1
16
(COMM
CTRL)
Relay Output 1
controlled by fieldbus.
40107 bit 0 or
00033
BO5 40 BO0
1404 RELAY
OUTPUT 2
16
(COMM
CTRL)
Relay Output 2
controlled by fieldbus.
40107 bit 1 or
00034
BO6 41 BO1
1407
RELAY
OUTPUT 3
16
(COMM
CTRL)
Relay Output 3
controlled by fieldbus.
40107 bit 2 or
00035
BO7 42 BO2
1410 RELAY
OUTPUT 4
16
(COMM
CTRL)
Relay Output 4
controlled by fieldbus.
40107 bit 3 or
00036
BO8 43 BO3
1413 RELAY
OUTPUT 5
16
(COMM
CTRL)
Relay Output 5
controlled by fieldbus.
40107 bit 4 or
00037
BO9 44 BO4
Bypass
Parameter
Value Setting
Protocol Reference
Modbus N2 FLN BACnet
0122
RO 1-3
STATUS
Relay 1…3
status.
N/A 40104 bit 0...2 or
00033...35
BI6…
BI8
76…
78
BI0…
BI2
0123
RO 4-5
STATUS
Relay 4…5
status.
N/A 40104 bit 3...4 or
00036...37
BI9…
B20
79…
80
BI3…
BI4