2-108 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
1. Reset by pressing UP & DOWN arrows simultaneously in edit mode. Save change by pressing
ENTER.
5307
(5007)
DV CRC
ERR
Rapidly
Increasing
Numeric
Value
1
1. Duplicate
Addresses
2. Too many devices
on wire
3. Noise on EIA-485
wire
1. See Corrective Action 1. Parameter
Number 5308 (5008)
2. Limit to 31 unit loads on 1 segment
(ACH550 = 1 unit load)
3. See Corrective Action 6. Parameter
Number 5308 (5008)
5309
(5009)
DV STATUS
IDLE 1. No network
connection
2. Blown EIA-485
transceiver
3. Wrong application
number (FLN only)
1. Land communication wires as shown in
drawings on page 1-188. Check
Repeater (if installed onsite)
2. See Corrective Action 7. Parameter
Number 5308 (5008)
3. Change application number in the
Siemens field panel.
5316
(5016)
DV PAR 16
(BACnet
Only)
Not
Increasing
Numeric
Value
1. Drive device
address parameter
5302 is set to 128 or
greater.
2. E-Clipse Bypass
device address
parameter 5002 is
set to 128 or greater.
3. Max Masters is set
too low on all drives.
1. Change parameter 5302 to a unique value
below 128.
2. Change parameter 5002 to a unique value
below 128.
Note: The default value for parameter
5002 is 256. This setting prevents the
network from seeing the bypass. Change
this setting ONLY if the bypass will be
seen as a node on the network.
3. Change Max Masters property at all
devices on bus to 127.
5306
(5006)
DV OK MSG
OK
Message
Counter not
increasing
1
1. Master/Client not
communicating with
drive.
2. Failed router
1. Add device and points to the building
control system.
2. Replace router.
Parameter
Number
Display on
Panel
(Symptom)
Possible Cause Corrective Action