2-112 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
Change of State (COS) enabled
Alarm Enabled
Warning Enabled
Override value is received, but there is no action taken.
Binary Input – The binary input objects support the following features:
Binary Input actual value
Normal / Alarm state specification
Alarm Enabled
Change of State (COS) enabled
Override value is received, but there is no action taken.
Analog Output – The analog output objects support the following features:
Analog Output value in engineering units
Override value is used to change the Analog Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
Binary Output – The binary output objects support the following features:
Binary Output value
Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
N2 analog input objects – drive
The following table lists the N2 Analog Input objects defined for the ACH550 drive.
N2 Analog Inputs:
Number Object
Drive
Parameter
Scale
Factor
Units Range
AI1 OUTPUT FREQUENCY 0103 10 Hz 0…250
AI2 RATED SPEED Note 1 10 % 0 …100
AI3 SPEED 0102 1 rpm 0 …9999
AI4 CURRENT 0104 10 A 0…9999
AI5 TORQUE 0105 10 % -200…200
AI6 POWER 0106 10 kW 0…65535
AI7 DRIVE TEMPERATURE 0110 10
°C0125
AI8 KILOWATT HOURS 0115 1 kWh 0…65535
AI9 MEGAWATT HOURS 0141 1 MWh 0…65535
AI10 RUN TIME 0114 1 H 0…65535
AI11 DC BUS VOLTAGE 0107 1 V 0…999
AI12 OUTPUT VOLTAGE 0109 1 V 0…999
AI13 PRC PID FEEDBACK 0130 10 % 0…100