ACH550 E-Clipse Bypass User’s Manual 2-163
Embedded fieldbus
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog input object instance summary – drive
The following table summarizes the Analog Input Objects supported:
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog output object instance summary – drive
The following table summarizes the Analog Output Objects supported:
BV19 CTL OVERRIDE
ACT
This object indicates whether
the drive is in BACnet Control
Override. (See BV18.)
ON/OFF R
BV20 START ENABLE 1 This object commands start
enable1. Control requires
param 1608 value = COMM.
ENABLE/
DISABLE
C
BV21 START ENABLE 2 This object commands start
enable1. Control requires
param 1609 value = COMM.
ENABLE/
DISABLE
C
Instance
ID
Object Name Description Units
Present Value
Access Type
AI0 ANALOG INPUT 1 This object indicates the value of
Analog Input 1. The corresponding
drive parameter is 0120.
Percent R
AI1 ANALOG INPUT 2 This object indicates the value of
Analog Input 2. The corresponding
drive parameter is 0121.
Percent R
Instance
ID
Object Name Description Units
Present Value
Access Type
AO0 AO 1
COMMAND
This object controls Analog Output 1. The
corresponding drive parameter is 0135,
COMM VALUE 1. Control requires parameter
1501 value = 135.
Percent C
AO1 AO 2
COMMAND
This object controls Analog Output 2. The
corresponding drive parameter is 0136,
COMM VALUE 2. Control requires parameter
1507 value = 136.
Percent C
Instance
ID
Object Name Description
Active/Inactive
Text
Present Value
Access Type