ACH550 E-Clipse Bypass User’s Manual 2-167
Embedded fieldbus
BACnet Protocol Implementation Conformance Statement
Date: March 1, 2008
Vendor Name: ABB, Inc
Product Name: ABB E-Clipse Bypass
Product Model Number: VCR, VDR, BCR, and BDR
Applications Software Version: 103F
Firmware Revision: 1508
BACnet Protocol Revision: 7
Product Description:
The ABB E-Clipse Bypass is an optional feature to the ACH550 high-
performance adjustable frequency drive specifically designed for
commercial automation applications. This product supports native
BACnet, connecting directly to the MS/TP LAN. All standard MS/TP baud
rates are supported, as well as master mode functionality. Over BACnet,
the drive and bypass can be fully controlled as a standard adjustable
frequency drive and a constant speed drive bypass. In addition, up to 24
configurable I/O are available over BACnet to the user application.
BACnet Standardized Device Profile
(Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building
Blocks Supported (Annex K):
DS-RP-B, DS-RPM-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B,
DM-RD-B
Segmentation Capability:
Segmented requests supported. Window Size ____
Segmented responses supported. Window Size ____
Standard Object Types Supported:
Object instantiation is static, i.e. objects cannot be created or deleted.
Refer to tables at end of this document for object details
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ___
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
MS/TP slave (Clause 9), baud rate(s): ___
Point-To-Point, EIA 232 (Clause 10), baud rate(s): ___
Point-To-Point, modem, (Clause 10), baud rate(s): ___
LonTalk, (Clause 11), medium: __________
Other: __________
Device Address Binding:
Is static device binding supported? (This is
currently necessary for two-way
communication with MS/TP slaves and
certain other devices.)
Yes
No
Networking Options:
Router, Clause 6 - List all routing configurations,
e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)