2-192 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
The drive control words when bypass parameter 1625 = (1) SYSTEM are
summarized in the following table. Note that these are written to the drive.
DRIVE CONTROL WORD
Bit ABB DRV LIM DCU PROFILE ABB DRV FULL
0 N/A N/A N/A
1 N/A N/A N/A
2 N/A REVERSE N/A
3 N/A N/A N/A
4 N/A RESET RAMP_OUT_ZERO
5 RAMP_HOLD EXT2 RAMP_HOLD
6 RAMP_IN_ZERO N/A RAMP_IN_ZERO
7 RESET STP_MODE_R RESET
8 N/A STP_MODE_EM N/A
9 N/A STP_MODE_C N/A
10 N/A RAMP_2 REMOTE_CMD (ref only)
11 EXT2 RAMP_OUT_0 EXT2
12 N/A RAMP_HOLD N/A
13 N/A RAMP_IN_0 N/A
14 N/A REQ_LOCALLOCK N/A
15 N/A TORQLIM2 N/A
16 N/A N/A N/A
17 N/A FBLOCAL_REF N/A
18 N/A N/A N/A
19 N/A N/A N/A
20-31 N/A Reserved N/A