ACH550 E-Clipse Bypass User’s Manual 2-215
Fieldbus adapter
8 AT_SETPOINT 1 OPERATING. Actual value equals (within tolerance limits) the
reference value.
0 Actual value is outside tolerance limits (not equal to
reference value).
9 REMOTE 1 Drive control location:
REMOTE (EXT1 or EXT2)
0 Drive control location: LOCAL
10 ABOVE_LIMIT 1 Supervised parameter’s value > supervision high limit.
Bit remains “1” until supervised parameter’s value <
supervision low limit.
See group 32, Supervision
0 Supervised parameter’s value < supervision low limit.
Bit remains “0” until supervised parameter’s value >
supervision high limit.
See group 32, Supervision
11 EXT CTRL LOC 1 External control location 2 (
EXT2) selected
0 External control location 1 (EXT1) selected
12 EXT RUN ENABLE 1 External Run Enable signal received
0 No External Run Enable signal received
13… 15 Unused
ABB Drives Profile (FBA) STATUS WORD
Bit Name Value
Description
(Correspond to states/boxes in the state diagram)